APCTEST(8) | System Manager's Manual | APCTEST(8) |
apctest
—
apcupsd(8) test program
apctest |
apctest
is a program that enables the
running of certain low-level tests to check the operation of the attached
simple signalling American Power Conversion Corp (APC) UPS and to check that
your apcupsd(8) configuration is correctly setup and can
establish communication with the UPS.
For an APC UPS operating in APC smart protocol mode,
apctest
enables the reading and programming of the
values of the UPS EEPROM configuration variables as well and the performing
of a battery runtime calibration. It also provides a simple TTY chat mode
which allows direct interaction with the UPS via the APC smart protocol. For
details of this protocol and the available commands, refer to the detailed
"APC Smart Protocol" section in the apcupsd manual.
IMPORTANT: Before running apctest
apctest
at the same
time.When run, apctest
displays a menu of
options which are different depending on whether the UPS is connected to a
USB port or to a serial port. For a serial port connection, there are two
different menus depending on whether the UPS is operating in APC smart
protocol mode or simple signalling mode - this also depends on which cable
is used to connect to the UPS. If a simple signalling cable is used to
connect to a Smart-UPS, the UPS will only be able to operate in simple
signalling mode.
apctest
saves a transcript of the session
to the file apctest.out in the directory from which
the program was called. Its content is useful for debugging purposes.
When using a UPS connected to a USB port (eg Back-UPS RS 1500), the following menu options will appear:
Performs a power down of the UPS into hibernate mode.
Performs an immediate self-test (switches to battery power to do so).
Displays the last self-test result.
Displays the current battery replacement date and optionally allows you to change it - useful when the battery is replaced so that you can accurately keep track of its age.
Displays the date the UPS was manufactured.
Sets the delay period before the UPS starts sounding its alarm when the utility power is lost.
Changes how sensitive the UPS is to the utility power quality and voltage fluctuations - (H)igh, (M)edium or (L)ow. The higher the sensitivity, the faster the UPS will switch to battery power or activate SmartBoost/SmartTrim (features that avoid using battery power provided the under/over voltage is within 12% of nominal). This setting should normally be set to High unless the UPS switches to battery power frequently, in which case a less sensitive setting will preserve UPS batteries... if the connected equipment can tolerate the power quality.
Sets the low voltage level at which the UPS switches to battery or activates SmartBoost.
Sets the high voltage level at which the UPS switches to battery or activates SmartTrim.
This performs a battery runtime calibration. This can only be performed if your battery is charged to 100% of capacity. The runtime calibration discharges the UPS battery to approximately 25% of capacity. The exact percentage depends on the UPS model.
The advantage of doing this calibration is that the UPS will recalibrate the remaining runtime counter that it maintains and therefore report a more accurate estimated runtime. As batteries age, they tend to hold less charge, so the UPS's internal runtime counter may not be accurate after several years.
It is recommended that battery runtime calibration be performed annually. Performing it too often shortens the lifetime of the UPS batteries.
This option will cause the UPS alarm beeper to sound for several seconds.
This option allows you to change the time interval between automatic UPS self-tests.
Exits from the program.
When using a UPS operating in APC smart protocol mode (eg a Smart-UPS) the following menu options will appear:
Selecting this option probes the UPS for all EEPROM configuration
variable values known to apctest
and displays them
in rather raw format. This output can be useful for providing technical
support if you are having problems with the behaviour of the UPS or
apcupsd(8).
This performs a battery runtime calibration. This can only be
performed if your battery is charged to 100% of capacity. The runtime
calibration discharges the UPS battery to approximately 25% of capacity. The
exact percentage depends on the UPS model. apctest
can optionally abort the calibration if it detects that the battery charge
is below 10%.
The advantage of doing this calibration is that the UPS will recalibrate the remaining runtime counter that it maintains and therefore report a more accurate estimated runtime. As batteries age, they tend to hold less charge, so the UPS's internal runtime counter may not be accurate after several years.
It is recommended that battery runtime calibration be performed annually. Performing it too often shortens the lifetime of the UPS batteries.
This option aborts an in progress battery runtime calibration.
Allows restarting of the monitoring of a battery runtime calibration.
Allows the programming of the values of a Smart-UPS's EEPROM configuration variables.
Choosing this option presents a sub-menu of programming options which are detailed below.
Prints the value of all EEPROM configuration variables known
to apctest
.
Changes the battery date - useful when the battery is replaced so that you can accurately keep track of its age.
Changes the UPS name - use no more than 8 characters to name the UPS.
Changes how sensitive the UPS is to the utility power quality and voltage fluctuations - (H)igh, (M)edium or (L)ow. The higher the sensitivity, the faster the UPS will switch to battery power or activate SmartBoost/SmartTrim (features that avoid using battery power provided the under/over voltage is within 12% of nominal). This setting should normally be set to High unless the UPS switches to battery power frequently, in which case a less sensitive setting will preserve UPS batteries... if the connected equipment can tolerate the power quality.
Changes the delay period before the UPS starts sounding its alarm when the utility power is lost.
Changes the remaining runtime minutes at which the UPS will send the low battery signal. When the UPS internally calculates that the specified number of minutes remains before battery power will be exhausted, it sends the low battery warning.
Changes the delay before the UPS restores power to connected equipment when the utility power returns after shutting down in hibernate mode.
Changes the delay for which the UPS waits before shutting off power to the connected equipment after being commanded to power down in hibernate mode.
Changes the low voltage level at which the UPS switches to battery or activates SmartBoost.
Changes the high voltage level at which the UPS switches to battery or activates SmartTrim.
Changes the battery charge percentage required after power down in hibernate mode before to the UPS will restore power to connected equipment on the return of utility power.
Changes the nominal voltage output when the UPS is running on battery power.
Changes or disables the automatic self-test interval.
This option allows the bulk programming of the EEPROM configuration variables from the values contained in the /etc/apcupsd.conf configuration file. Refer to the "APCTEST EEPROM CONFIGURATION DIRECTIVES" section of the man page for apcupsd.conf(5)
This option exits back to the previous (main) menu.
This option allows direct interaction with the attached UPS using the APC smart protocol commands.
WARNING: Take special care what commands you enter because it is possible to cause the UPS to suddenly shutdown or, in the worst case, modify the UPS in such a way as to permanently disable it. Do NOT experiment with unknown or unsupported commands. Caveat Utilitor!
Exits from the program.
When using an APC UPS operating in simple signalling mode the following menu options will appear:
The test result depends on the model of UPS and type of cable being used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.
The test result depends on the model of UPS and type of cable being used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.
The test result depends on the model of UPS and type of cable being used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.
The test result depends on the model of UPS and type of cable being used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.
The test result depends on the model of UPS and type of cable being used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.
The test result depends on the model of UPS and type of cable being used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.
This option has apctest
guess which cable
should be used with the attached UPS.
Exits from the program.
/etc/apcupsd/apcupsd.conf default configuration file
apctest.out transcript of the
apctest
session
The HTML apcupsd manual installed on your system or available online at http://www.apcupsd.org/
Trevor Roydhouse (current)
Robert Huff
Adam Kropelin (current Project Manager and Code
Maintainer)
Kern Sibbald (former Project Manager and Code
Maintainer)
Riccardo Facchetti (former Project Manager and Code
Maintainer)
Andre M. Hedrick (Project Founder and former Code
Maintainer)
An enormous number of users who have devoted their time and energy to this project -- thanks.
January 10, 2009 | apctest v3.14.6 |