UPSMON.CONF(5) | NUT Manual | UPSMON.CONF(5) |
upsmon.conf - Configuration for Network UPS Tools upsmon
This file’s primary job is to define the systems that upsmon(8) will monitor and to tell it how to shut down the system when necessary. It will contain passwords, so keep it secure. Ideally, only the upsmon process should be able to read it.
Additionally, other optional configuration values can be set in this file.
DEADTIME seconds
upsmon requires a UPS to provide status information every few seconds (see POLLFREQ and POLLFREQALERT) to keep things updated. If the status fetch fails, the UPS is marked stale. If it stays stale for more than DEADTIME seconds, the UPS is marked dead.
A dead UPS that was last known to be on battery is assumed to have changed to a low battery condition. This may force a shutdown if it is providing a critical amount of power to your system. This seems disruptive, but the alternative is barreling ahead into oblivion and crashing when you run out of power.
Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT. Otherwise, you’ll have "dead" UPSes simply because upsmon isn’t polling them quickly enough. Rule of thumb: take the larger of the two POLLFREQ values, and multiply by 3.
FINALDELAY seconds
If you need to let your users do something in between those events, increase this number. Remember, at this point your UPS battery is almost depleted, so don’t make this too big.
Alternatively, you can set this very low so you don’t wait around when it’s time to shut down. Some UPSes don’t give much warning for low battery and will require a value of 0 here for a safe shutdown.
HOSTSYNC seconds
When a UPS goes critical (on battery + low battery, or "FSD": forced shutdown), the slaves are supposed to disconnect and shut down right away. The HOSTSYNC timer keeps the master upsmon from sitting there forever if one of the slaves gets stuck.
This value is also used to keep slave systems from getting stuck if the master fails to respond in time. After a UPS becomes critical, the slave will wait up to HOSTSYNC seconds for the master to set the FSD flag. If that timer expires, the slave will assume that the master is broken and will shut down anyway.
This keeps the slaves from shutting down during a short-lived status change to "OB LB" that the slaves see but the master misses.
MINSUPPLIES num
Large/expensive server type systems usually have more, and can run with a few missing. The HP NetServer LH4 can run with 2 out of 4, for example, so you’d set it to 2. The idea is to keep the box running as long as possible, right?
Obviously you have to put the redundant supplies on different UPS circuits for this to make sense! See big-servers.txt in the docs subdirectory for more information and ideas on how to use this feature.
Also see the section on "power values" in upsmon(8).
MONITOR system powervalue username password type
You must have at least one MONITOR directive in upsmon.conf.
system is a UPS identifier. It is in this form:
<upsname>[@<hostname>[:<port>]]
The default hostname is "localhost". Some examples:
powervalue is an integer representing the number of power supplies that the UPS feeds on this system. Most normal computers have one power supply, and the UPS feeds it, so this value will be 1. You need a very large or special system to have anything higher here.
You can set the powervalue to 0 if you want to monitor a UPS that doesn’t actually supply power to this system. This is useful when you want to have upsmon do notifications about status changes on a UPS without shutting down when it goes critical.
The username and password on this line must match an entry in that system’s upsd.users(5). If your username is "monmaster" and your password is "blah", the MONITOR line might look like this:
MONITOR myups@bigserver 1 monmaster blah master
Meanwhile, the upsd.users on bigserver would look like this:
[monmaster]
password = blah
upsmon master # (or slave)
The type refers to the relationship with upsd(8). It can be either "master" or "slave". See upsmon(8) for more information on the meaning of these modes. The mode you pick here also goes in the upsd.users file, as seen in the example above.
NOCOMMWARNTIME seconds
NOTIFYCMD command
This command is called with the full text of the message as one argument. The environment string NOTIFYTYPE will contain the type string of whatever caused this event to happen.
If you need to use upssched(8), then you must make it your NOTIFYCMD by listing it here.
Note that this is only called for NOTIFY events that have EXEC set with NOTIFYFLAG. See NOTIFYFLAG below for more details.
Making this some sort of shell script might not be a bad idea. For more information and ideas, see docs/scheduling.txt
Remember, this command also needs to be one element in the configuration file, so if your command has spaces, then wrap it in quotes.
NOTIFYCMD "/path/to/script --foo --bar"
This script is run in the background—that is, upsmon forks before it calls out to start it. This means that your NOTIFYCMD may have multiple instances running simultaneously if a lot of stuff happens all at once. Keep this in mind when designing complicated notifiers.
NOTIFYMSG type message
NOTIFYMSG ONLINE "UPS %s is getting line power"
NOTIFYMSG ONBATT "Someone pulled the plug on %s"
Note that %s is replaced with the identifier of the UPS in question.
The message must be one element in the configuration file, so if it contains spaces, you must wrap it in quotes.
NOTIFYMSG NOCOMM "Someone stole UPS %s"
Possible values for type:
ONLINE
ONBATT
LOWBATT
FSD
COMMOK
COMMBAD
SHUTDOWN
REPLBATT
NOCOMM
NOTIFYFLAG type flag[+flag][+flag]...
Examples:
NOTIFYFLAG ONLINE SYSLOG NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
Possible values for the flags:
SYSLOG
WALL
EXEC
IGNORE
If you use IGNORE, don’t use any other flags on the same line.
POLLFREQ seconds
There are some catches. First, if you set the POLLFREQ too high, you may miss short-lived power events entirely. You also risk triggering the DEADTIME (see above) if you use a very large number.
Second, there is a point of diminishing returns if you set it too low. While upsd normally has all of the data available to it instantly, most drivers only refresh the UPS status once every 2 seconds. Polling any more than that usually doesn’t get you the information any faster.
POLLFREQALERT seconds
This should always be equal to or lower than the POLLFREQ value. By default it is also set 5 seconds.
The warnings from the POLLFREQ entry about too-high and too-low values also apply here.
POWERDOWNFLAG filename
This is done to forcibly reset the slaves, so they don’t get stuck at the "halted" stage even if the power returns during the shutdown process. This usually does not work well on contact-closure UPSes that use the genericups driver.
See the config-notes.txt file in the docs subdirectory for more information. Refer to the section:
"Configuring automatic shutdowns for low battery events", or refer to the online version.
RBWARNTIME seconds
If you need another value, set it here.
RUN_AS_USER username
The catch is that "nobody" can’t read your upsmon.conf, since by default it is installed so that only root can open it. This means you won’t be able to reload the configuration file, since it will be unavailable.
The solution is to create a new user just for upsmon, then make it run as that user. I suggest "nutmon", but you can use anything that isn’t already taken on your system. Just create a regular user with no special privileges and an impossible password.
Then, tell upsmon to run as that user, and make upsmon.conf readable by it. Your reloads will work, and your config file will stay secure.
This file should not be writable by the upsmon user, as it would be possible to exploit a hole, change the SHUTDOWNCMD to something malicious, then wait for upsmon to be restarted.
SHUTDOWNCMD command
When upsmon is a master, it will allow any slaves to log out before starting the local shutdown procedure.
Note that the command needs to be one element in the config file. If your shutdown command includes spaces, then put it in quotes to keep it together, i.e.:
SHUTDOWNCMD "/sbin/shutdown -h +0"
CERTPATH certificate file or database
With NSS:
With OpenSSL:
CERTIDENT certificate name database password
CERTHOST hostname certificate name certverify forcessl
Each entry maps server name with the expected certificate name and flags indicating if the server certificate is verified and if the connection must be secure.
CERTVERIFY 0 | 1
Without this, there is no guarantee that the upsd is the right host. Enabling this greatly reduces the risk of man-in-the-middle attacks. This effectively forces the use of SSL, so don’t use this unless all of your upsd hosts are ready for SSL and have their certificates in order.
When compiled with NSS support of SSL, can be overriden for host specified with a CERTHOST directive.
FORCESSL 0 | 1
If you don’t use CERTVERIFY 1, then this will at least make sure that nobody can sniff your sessions without a large effort. Setting this will make upsmon drop connections if the remote upsd doesn’t support SSL, so don’t use it unless all of them have it running.
When compiled with NSS support of SSL, can be overriden for host specified with a CERTHOST directive.
upsmon(8), upsd(8), nutupsdrv(8).
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
12/29/2015 | Network UPS Tools 2.7.3. |