DOKK / manpages / debian 12 / libmodbus-dev / modbus_read_bits.3.en
MODBUS_READ_BITS(3) libmodbus Manual MODBUS_READ_BITS(3)

modbus_read_bits - read many bits

int modbus_read_bits(modbus_t *ctx, int addr, int nb, uint8_t *dest);

The modbus_read_bits() function shall read the status of the nb bits (coils) to the address addr of the remote device. The result of reading is stored in dest array as unsigned bytes (8 bits) set to TRUE or FALSE.

You must take care to allocate enough memory to store the results in dest (at least nb * sizeof(uint8_t)).

The function uses the Modbus function code 0x01 (read coil status).

The function shall return the number of read bits if successful. Otherwise it shall return -1 and set errno.

EMBMDATA

Too many bits requested

modbus_write_bit(3) modbus_write_bits(3)

The libmodbus documentation was written by Stéphane Raimbault <stephane.raimbault@gmail.com>

10/15/2022 libmodbus v3.1.6