DOKK / manpages / debian 12 / nut-server / nutdrv_qx.8.en
NUTDRV_QX(8) NUT Manual NUTDRV_QX(8)

nutdrv_qx - Driver for Q* protocol serial and USB based UPS equipment

This man page only documents the hardware-specific features of the nutdrv_qx driver. For information about the core driver, see nutupsdrv(8).

The nutdrv_qx driver is known to work with various UPSes from Armac, Blazer, Energy Sistem, Fenton Technologies, General Electric, Hunnox, Masterguard, Mustek, Powercool, Voltronic Power (rebranded by many, many - have I said many? - others...

Long story short: if your UPS came with a software called Viewpower, chances are high that it works with this driver with one of the voltronic* protocols or with the mecer one), and many others.

The NUT compatibility table lists all the known supported models. Keep in mind, however, that other models not listed there may also be supported, but haven’t been tested or reported back.

All devices with a serial interface and many with a USB interface are supported.

You may need to override or provide defaults for some values, depending on the make and model of your UPS.

The following are the ones that most likely will need changing (see ups.conf(5)):

ondelay = value

Time to wait before switching on the UPS (seconds). This value is truncated to units of 60 seconds.

Note that a value below 3 minutes, may cause earlier firmware versions to not switch on automatically, so it defaults to 3 minutes (i.e. 180 seconds).

This option provides a default value for ups.delay.start that will then be used by the driver in the automatic shutdown sequence (i.e. calling the driver with the -k option, calling upsdrvctl(8) with the shutdown option or when the FSD flag is set and upsmon(8) enters its shutdown sequence): however you can change this value ‘on the fly’ for the actual session, only for the use with instant commands, setting ups.delay.start with upsrw(8).

offdelay = value

Time to wait before shutting down the UPS (seconds). This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds). Defaults to 30 seconds.

This option provides a default value for ups.delay.shutdown that will then be used by the driver in the automatic shutdown sequence (i.e. calling the driver with the -k option, calling upsdrvctl(8) with the shutdown option or when the FSD flag is set and upsmon(8) enters its shutdown sequence): however you can change this value ‘on the fly’ for the actual session, only for the use with instant commands, setting ups.delay.shutdown with upsrw(8).

stayoff

If you set stayoff in ups.conf(5) when FSD arises the UPS will call a shutdown.stayoff shutting down after ups.delay.shutdown seconds and won’t return (see KNOWN PROBLEMS), otherwise (standard behaviour) the UPS will call shutdown.return shutting down after ups.delay.shutdown seconds and then turn on after ups.delay.start seconds (if mains meanwhile returned).

protocol = string

Skip autodetection of the protocol to use and only use the one specified. Supported values: bestups, hunnox, masterguard, mecer, megatec, megatec/old, mustek, q1, voltronic, voltronic-qs, voltronic-qs-hex and zinto.

Note that if you end up using the q1 protocol, you may want to give a try to the mecer, megatec and zinto ones setting the novendor/norating flags (only one, or both).

pollfreq = num

Set polling interval for full updates, in seconds, to reduce the message traffic. Between two polling requests, the driver will do quick polls dealing just with ups.status at an interval specified by the pollinterval driver option (details in ups.conf(5)). The default value is 30 (in seconds).

If your UPS doesn’t report either battery.charge or battery.runtime you may want to add the following ones in order to have guesstimated values:

default.battery.voltage.high = value

Maximum battery voltage that is reached after about 12 to 24 hours charging. If you want the driver to report a guesstimated battery.charge, you need to specify this (see BATTERY CHARGE).

default.battery.voltage.low = value

Minimum battery voltage just before the UPS automatically shuts down. If you want the driver to report a guesstimated battery.charge, you need to specify this (see BATTERY CHARGE).

default.battery.voltage.nominal = value, override.battery.voltage.nominal = value

Some devices show a wrong nominal battery voltage (or none at all), so you may need to override or set a default value.

override.battery.packs = value

Some devices report a part of the total battery voltage. For instance, if battery.voltage.nominal is 24 V, but it reports a battery.voltage of around 2 V, the number of battery.packs to correct this reading would be 12. The driver will attempt to detect this automatically, but if this fails somehow, you may want to override this value.

runtimecal = value,value,value,value

Parameter used in the (optional) runtime estimation. This takes two runtimes at different loads. Typically, this uses the runtime at full load and the runtime at half load. For instance, if your UPS has a rated runtime of 240 seconds at full load and 720 seconds at half load, you would enter

runtimecal = 240,100,720,50

The first load should always be higher than the second. If you have values available for loads other than 100 and 50 % respectively, you can use those too, but keep them spaced apart as far as reasonably possible. Just don’t get too close to no load (prediction of runtime depends more on idle load for the battery then).

chargetime = value

The time needed to fully recharge the battery after being fully discharged. If not specified, the driver defaults to 43200 seconds (12 hours). Only used if runtimecal is also specified.

idleload = value

Minimum battery load used by the driver to estimate the runtime. If not specified, the driver defaults to 10%. Only used if runtimecal is also specified.

ignoresab

Some UPSes incorrectly report the ‘Shutdown Active’ bit as always on, consequently making the driver believe the UPS is nearing a shutdown (and, as a result, ups.status always contains FSD... and you know what this means). Setting this flag will make the driver ignore the ‘Shutdown Active’ bit.

ondelay

The acceptable range is 0..599940 seconds.

offdelay

The acceptable range is 12..600 seconds.

norating

Some UPSes will lock up if you attempt to read rating information from them. Setting this flag will make the driver skip this step.

novendor

Some UPSes will lock up if you attempt to read vendor information from them. Setting this flag will make the driver skip this step.

ondelay

The acceptable range is 60..599940 seconds.

offdelay

The acceptable range is 12..5940 seconds.

pins_shutdown_mode = value

Set shutdown mode functionality of Pin 1 and Pin 7 on the UPS DB9 communication port (Per Best Power’s EPS-0059) to value [0..6].

MASTERGUARD PROTOCOL

slave_addr = value

Make the claim function verify it’s talking to the specified slave address (ups.id). Safeguard against talking to the wrong one of several identical UPSes on the same USB bus. Note that when changing ups.id (through upsrw(8)) the driver will continue to talk to the UPS with the new slave address, but won’t claim it again on restart until the slave_addr parameter is adjusted.

ondelay

The acceptable range is 0..599940 seconds.

offdelay

The acceptable range is 12..600 seconds.

VOLTRONIC-QS, VOLTRONIC-QS-HEX PROTOCOLS

ondelay

The acceptable range is 60..599940 seconds.

offdelay

The acceptable range is 12..540 seconds.

VOLTRONIC PROTOCOL

The following options are supported only by the voltronic protocol. Not all of them are available on all the UPSes supported by this protocol.

ondelay

The acceptable range is 0..599940 seconds.

offdelay

The acceptable range is 12..5940 seconds.

battery_number = value

Set number of batteries that make a pack to value [1..9]. This setting will change the charge and runtime estimation reported by the UPS.

output_phase_angle = value

Changes output phase angle to the provided value [000, 120, 180, 240]°.

UPS CAPABILITY SETTINGS

reset_to_default

Reset capability options and their voltage and frequency limits to safe default values. (Doable only when the UPS is in Standby Mode)

Note that setting this option will reset also ups.start.auto, battery.protection, battery.energysave, ups.start.battery, outlet.0.switchable, input.transfer.high, input.transfer.low, input.frequency.high and input.frequency.low.

These UPSes can be fine-tuned to suit your needs enabling or disabling the following options (the driver should tell you which one the UPS is capable of on startup: the settable ones will be reported either are enabled or disabled in the logs):

alarm_control = string

Enable or disable alarm (BEEP!) [enabled/disabled]. Settable also ‘on the fly’ with beeper.enable and beeper.disable instant commands.

bypass_alarm = string

Enable or disable alarm (BEEP!) at Bypass Mode [enabled/disabled].

battery_alarm = string

Enable or disable alarm (BEEP!) at Battery Mode [enabled/disabled].

bypass_when_off = string

Enable or disable bypass when the UPS is Off [enabled/disabled]. If enabled, AC will directly provide power to connected devices when the UPS is off.

bypass_forbidding = string

Enable or disable Bypass Forbidding [enabled/disabled]. If enabled, the UPS will not transfer to bypass mode under any condition.

converter_mode = string

Enable or disable Converter Mode [enabled/disabled]. When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode.

eco_mode = string

Enable or disable ECO Mode [enabled/disabled]. When input voltage/frequency are within acceptable range, the UPS will bypass voltage to output for energy saving. PFC and INVERTER are still active at this mode. Settable also ‘on the fly’ with bypass.start and bypass.stop instant commands.

advanced_eco_mode = string

Enable or disable Advanced ECO Mode [enabled/disabled]. When input voltage/frequency are within acceptable range, the UPS will bypass voltage to output for energy saving. PFC and INVERTER are off at this mode.

battery_open_status_check = string

Enable or disable Battery Open Status Check [enabled/disabled]. If enabled, when the UPS is turned on, it will check if the battery is connected or not.

site_fault_detection = string

Enable or disable site fault detection [enabled/disabled]. If enabled, the UPS will beep when the input neutral and hot wires are reversed.

constant_phase_angle = string

Enable or disable Constant Phase Angle Function (output and input phase angles are not equal) [enabled/disabled].

limited_runtime_on_battery = string

Enable or disable limited runtime on battery mode [enabled/disabled].

BYPASS MODE VOLTAGE/FREQUENCY LIMITS

Variables to fine-tune voltage and frequency limits for Bypass mode. These limits are reset to safe default values by reset_to_default.

If AC voltage and frequency are within acceptable range, Bypass mode will be used (If the UPS is capable of and it’s enabled).

Since these values are device-specific, if your UPS support them, you will get their settable limits printed in the logs on startup.

max_bypass_volt = value

Maximum voltage for Bypass Mode (V).

min_bypass_volt = value

Minimum voltage for Bypass Mode (V).

max_bypass_freq = value

Maximum frequency for Bypass Mode (Hz).

min_bypass_freq = value

Minimum frequency for Bypass Mode (Hz).

OPTIONS SPECIFIC FOR P31 UPSES

The following options are available only on P31 UPSes.

work_range_type = string

Device grid working range for P31 UPSes [Appliance/UPS].

TESTING

This protocol comes with a couple of functions that are not enabled by default because of the lack of knowledge of some part of the communication protocol used by these UPSes by your friendly neighborhood developer. Since these functions are supposed to be queries to the UPS for some kind of information, they should not make your UPS go boom. So if you are brave enough to risk your UPS and attached devices' life to help the developers, this will be very appreciated.. Do it at your own risk.

testing

If invoked the driver will exec also commands that still need testing.

cablepower = string

By default the driver will set DTR and clear RTS (normal). If you find that your UPS isn’t detected or the communication with the UPS is unreliable, you may try if clear DTR and set RTS (reverse), set DTR and RTS (both) or clear DTR and RTS (none) improves this situation.

port = string

You must set value to auto.

vendorid = regex, productid = regex, vendor = regex, product = regex, serial = regex

Select a specific UPS, in case there is more than one connected via USB. Each option specifies an extended regular expression (see regex(7)) that must match the UPS’s entire vendor/product/serial string (minus any surrounding whitespace), or the whole 4-digit hexadecimal code for vendorid and productid. Try -DD for finding out the strings to match.

Examples:

•-x vendor="Foo.Corporation.*"

•-x vendorid=051d* (APC)

•-x product=".*(Smart|Back)-?UPS.*"

bus = regex

Select a UPS on a specific USB bus or group of buses. The argument is a regular expression that must match the bus name where the UPS is connected (e.g. bus="002", bus="00[2-3]").

device = regex

Select a UPS on a specific USB device or group of devices. The argument is a regular expression that must match the device name where the UPS is connected (e.g. device="001", device="00[1-2]"). Note that device numbers are not guaranteed by the OS to be stable across re-boots or device re-plugging.

subdriver = string

Select a serial-over-USB subdriver to use. You have a choice between cypress, fabula, fuji, hunnox, ippon, krauler, phoenix, phoenixtec, sgs, snr, armac and ablerex. When using this option, it is mandatory to also specify the vendorid and productid.

langid_fix = value

Apply the language ID workaround to the krauler subdriver. This is mandatory for some devices to work (LDLC, Dynamix and others). You must provide value (0x409 or 0x4095), according to your device entry in NUT hardware compatibility list (HCL).

noscanlangid

If this flag is set, don’t autoscan valid range for langid.

IMPLEMENTATION NOTES

armac subdriver

The Armac communication subdriver reproduces a communication protocol used by an old release of "PowerManagerII" software, which doesn’t seem to be Armac specific: its banner is "2004 Richcomm Technologies, Inc. Dec 27 2005 ver 1.1." Maybe other Richcomm UPSes would work with this — maybe better than with the older standalone richcomm_usb driver.

fabula subdriver

This subdriver, meant to be used with the megatec protocol, does not support the various test.battery commands. Plus, the shutdown.return command ignores the values set in ups.delay.start/ondelay and makes the UPS turn on the load as soon as power is back.

hunnox subdriver

This protocol subdriver is closely related to fabula one, with a few tweaks for devices not directly supported by that driver.

fuji subdriver

This subdriver, meant to be used with the megatec protocol, does not support the shutdown.stayoff and load.off commands. Plus, the shutdown.return command ignores the values set in ups.delay.start/ondelay and makes the UPS turn on the load as soon as power is back.

krauler subdriver

This subdriver, meant to be used with the megatec protocol, does not support the shutdown commands, i.e.: shutdown.return, shutdown.stayoff and load.off.

snr subdriver

This subdriver, meant to be used with the megatec protocol, does not support the shutdown commands, i.e.: shutdown.return, shutdown.stayoff and load.off.

This driver supports some instant commands (see upscmd(8)):

beeper.toggle

Toggle the UPS beeper. (Not available on some hardware)

load.on

Turn on the load immediately. (Not available on some hardware)

load.off

Turn off the load immediately (see KNOWN PROBLEMS).

shutdown.return

Turn off the load and return when power is back. Uses the timers defined by ups.delay.start and ups.delay.shutdown.

shutdown.stayoff

Turn off the load and remain off (see KNOWN PROBLEMS). Uses the timer defined by ups.delay.shutdown.

shutdown.stop

Stop a shutdown in progress.

test.battery.start.deep

Perform a long battery test. (Not available on some hardware)

test.battery.start.quick

Perform a quick (10 second) battery test.

test.battery.stop

Stop a running battery test. (Not available on some hardware)

test.battery.start value

Perform a battery test for the duration of value seconds (truncated to 60 seconds) [60..5940].

MASTERGUARD PROTOCOL

beeper.enable

Enable the UPS beeper.

beeper.disable

Disable the UPS beeper.

test.battery.start value

Perform a battery test for the duration of value seconds (truncated to 60 seconds) [0..5940]. This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds).

bypass.start

Put the UPS in bypass mode

bypass.stop

Take the UPS in normal mode

VOLTRONIC POWER P98 UNITS (WITH MECER PROTOCOL)

test.battery.start value

Perform a battery test for the duration of value seconds (truncated to 60 seconds) [12..5940]. This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds).

VOLTRONIC PROTOCOL

The following instant commands are available for the voltronic protocol. Not all of them are available on all the UPSes supported by this protocol.

beeper.enable

Enable the UPS beeper.

beeper.disable

Disable the UPS beeper.

test.battery.start value

Perform a battery test for the duration of value seconds [12..5940]. This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds).

outlet.1.load.off

Turn off outlet 1 load immediately.

outlet.1.load.on

Turn on outlet 1 load immediately.

outlet.2.load.off

Turn off outlet 2 load immediately.

outlet.2.load.on

Turn on outlet 2 load immediately.

outlet.3.load.off

Turn off outlet 3 load immediately.

outlet.3.load.on

Turn on outlet 3 load immediately.

outlet.4.load.off

Turn off outlet 4 load immediately.

outlet.4.load.on

Turn on outlet 4 load immediately.

bypass.start

Put the UPS in ECO Mode.

bypass.stop

Take the UPS out of ECO Mode.

Due to popular demand, this driver will report a guesstimated battery.charge and optionally battery.runtime, provided you specified a couple of the EXTRA ARGUMENTS listed above.

If you specify both battery.voltage.high and battery.voltage.low in ups.conf(5), but don’t enter runtimecal, it will guesstimate the state of charge by looking at the battery voltage alone. This is not reliable under load, as this only gives reasonably accurate readings if you disconnect the load, let the battery rest for a couple of minutes and then measure the open cell voltage. This just isn’t practical if the power went out and the UPS is providing power for your systems.


battery.voltage - battery.voltage.low battery.charge = ------------------------------------------ x 100 %
battery.voltage.high - battery.voltage.low

There is a way to get better readings without disconnecting the load but this requires one to keep track on how much (and how fast) current is going in and out of the battery. If you specified the runtimecal, the driver will attempt to do this. Note however, that this heavily relies on the values you enter and that the UPS must be able to report the load as well. There are quite a couple of devices that report 0 % (or any other fixed value) at all times, in which case this obviously doesn’t work.

The driver also has no way of determining the degradation of the battery capacity over time, so you’ll have to deal with this yourself (by adjusting the values in runtimecal). Also note that the driver guesses the initial state of charge based on the battery voltage, so this may be less than 100 %, even when you are certain that they are full. There is just no way to reliably measure this between 0 and 100 % full charge.

This is better than nothing (but not by much). If any of the above calculations is giving you incorrect readings, you are the one that put in the values in ups.conf(5), so don’t complain with the author. If you need something better, buy a UPS that reports battery.charge and battery.runtime all by itself without the help of a NUT driver.

The nutdrv_qx driver having replaced the megatec ones, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following megatec options, in ups.conf(5), have to be changed:

battvolts

You need to use default.battery.voltage.high and default.battery.voltage.low

dtr and rts

You need to use cablepower

ignoreoff

This parameter can simply be discarded, since it was a wrong understanding of the specification.

The nutdrv_qx driver having replaced the blazer ones, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following blazer options, in ups.conf(5), have to be changed:

ondelay

While the previous blazer drivers expected minutes, the new nutdrv_qx driver wants seconds.

The following instant command has also been changed:

test.battery.start value

While the old blazer drivers expected a value in minutes, the nutdrv_qx driver wants a value in seconds.

The nutdrv_qx driver having replaced the bestups one, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following bestups options, in ups.conf(5), are no longer supported by this driver:

nombattvolt, battvoltmult

See BATTERY CHARGE.

ID

Discarded.

The nutdrv_qx driver having replaced the voltronic ones, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following voltronic options, in ups.conf(5), have to be changed:

ondelay

While the previous voltronic drivers expected minutes, the new nutdrv_qx driver wants seconds. It no longer defaults to 0 minutes but to 3 minutes (i.e. 180 seconds) for compatibility with the users switching from the old blazer drivers.

battnumb

This option has been renamed to battery_number.

The following options are no longer supported by this driver, you can now change them more conveniently ‘on the fly’ calling upsrw(8) with the appropriate NUT variable - provided that your UPS supports them.

battpacks battery.packs Set number of battery packs in parallel [1..99]. This setting will change the charge and runtime estimation reported by the UPS.
battlow battery.voltage.low Set minimum battery voltage just before the UPS automatically shuts down. This setting will change the charge and runtime estimation reported by the UPS.
auto_reboot ups.start.auto Enable or disable auto reboot [enabled/disabled]. If enabled, the UPS will auto recover when AC power returns.
battery_protection battery.protection Enable or disable battery deep discharge protection [enabled/disabled].
energy_saving battery.energysave Enable or disable Green power function [enabled/disabled]. If enabled, for energy saving, the UPS will auto off when there is no load.
cold_start ups.start.battery Enable or disable Cold Start [enabled/disabled]. If enabled, the UPS can be turned on also if AC is not connected to the UPS.
outlet_control outlet.0.switchable Enable or disable programmable outlets control at battery mode [enabled/disabled]. If enabled, the UPS will cut off programmable outlets after backup time (set through outlet.{1,2,3,4}.delay.shutdown) arrives. If disabled, the UPS will provide continuous power to programmable outlets until the battery is running out.
max_eco_volt input.transfer.high Maximum voltage for ECO Mode (V). If AC voltage is within acceptable range, ECO mode will be used (If the UPS is capable of and it’s enabled).
min_eco_volt input.transfer.low Minimum voltage for ECO Mode (V). If AC voltage is within acceptable range, ECO mode will be used (If the UPS is capable of and it’s enabled).
max_eco_freq input.frequency.high Maximum frequency for ECO Mode (Hz). If AC frequency is within acceptable range, ECO mode will be used (If the UPS is capable of and it’s enabled).
min_eco_freq input.frequency.low Minimum frequency for ECO Mode (Hz). If AC frequency is within acceptable range, ECO mode will be used (If the UPS is capable of and it’s enabled).
outlet1_delay outlet.1.delay.shutdown Delay time before programmable outlet 1 shuts down the load when on battery mode [0..59940] (seconds).
outlet2_delay outlet.2.delay.shutdown Delay time before programmable outlet 2 shuts down the load when on battery mode [0..59940] (seconds).
outlet3_delay outlet.3.delay.shutdown Delay time before programmable outlet 3 shuts down the load when on battery mode [0..59940] (seconds).
outlet4_delay outlet.4.delay.shutdown Delay time before programmable outlet 4 shuts down the load when on battery mode [0..59940] (seconds).
batt_type battery.type Battery type (for P31 UPSes only) [Li/Flooded/AGM].

Some UPS commands aren’t supported by all models. In most cases, the driver will send a message to the system log when the user tries to execute an unsupported command. Unfortunately, some models don’t even provide a way for the driver to check for this, so the unsupported commands will silently fail.

Both the load.off and shutdown.stayoff instant commands are meant to turn the load off indefinitely. However, some UPS models don’t allow this.

Some models report a bogus value for the beeper status (will always be enabled or disabled). So, the beeper.toggle command may appear to have no effect in the status reported by the driver when, in fact, it is working fine.

The temperature and load value is known to be bogus in some models.

The driver is supposed to support both "new" A series (A700/1000/2000/3000 and their -19 cousins) and E series (E60/100/200) but was tested only on A due to lack of E hardware.

VOLTRONIC-QS UNITS

Both load.off and shutdown.stayoff instant commands are known to work as expected (i.e. turn the load off indefinitely) only if mains is present, otherwise, as soon as mains returns the load will be powered.

After issuing a shutdown.return instant command, the UPS won’t wait ondelay before powering on the load, provided the following conditions are met:

•if the load has been previously (no matter how long before) powered off through load.off/shutdown.stayoff and powered on through load.on/shutdown.stop and

•if AC wasn’t cut after issuing the load.off/shutdown.stayoff (i.e. the UPS didn’t turn itself off) and

•if there’s a power outage after issuing the shutdown.return command

In this case, as soon as mains returns the load will be powered.

VOLTRONIC-QS-HEX UNITS

shutdown.return, load.off, and shutdown.stayoff instant commands are known to work as expected only if mains is present, otherwise, as soon as mains returns the load will be powered.

The UPSes supported by voltronic protocol report warnings through a 64bit flag (bit1bit2...bit63bit64) where 1 means that a warning arose, while 0 means no warning. Since more than one warning at a time can be signaled, and because of the limited space in the ups.alarm variable, if the length of the warnings exceeds that of ups.alarms variable, they will be reported as bits. If you want to know the explanation of that bit you can either watch the log or see the next table (unlisted bits equal to unknown warnings).

Table 1. UPS Warnings for voltronic UPSes

# Corresponding Warning
1 Battery disconnected
2 Neutral not connected
3 Site fault
4 Phase sequence incorrect
5 Phase sequence incorrect in bypass
6 Input frequency unstable in bypass
7 Battery overcharged
8 Low battery
9 Overload alarm
10 Fan alarm
11 EPO enabled
12 Unable to turn on UPS
13 Over temperature alarm
14 Charger alarm
15 Remote auto shutdown
16 L1 input fuse not working
17 L2 input fuse not working
18 L3 input fuse not working
19 Positive PFC abnormal in L1
20 Negative PFC abnormal in L1
21 Positive PFC abnormal in L2
22 Negative PFC abnormal in L2
23 Positive PFC abnormal in L3
24 Negative PFC abnormal in L3
25 Abnormal in CAN-bus communication
26 Abnormal in synchronous signal circuit
27 Abnormal in synchronous pulse signal circuit
28 Abnormal in host signal circuit
29 Male connector of parallel cable not connected well
30 Female connector of parallel cable not connected well
31 Parallel cable not connected well
32 Battery connection not consistent in parallel systems
33 AC connection not consistent in parallel systems
34 Bypass connection not consistent in parallel systems
35 UPS model types not consistent in parallel systems
36 Capacity of UPSs not consistent in parallel systems
37 Auto restart setting not consistent in parallel systems
38 Battery cell over charge
39 Battery protection setting not consistent in parallel systems
40 Battery detection setting not consistent in parallel systems
41 Bypass not allowed setting not consistent in parallel systems
42 Converter setting not consistent in parallel systems
43 High loss point for frequency in bypass mode not consistent in parallel systems
44 Low loss point for frequency in bypass mode not consistent in parallel systems
45 High loss point for voltage in bypass mode not consistent in parallel systems
46 Low loss point for voltage in bypass mode not consistent in parallel systems
47 High loss point for frequency in AC mode not consistent in parallel systems
48 Low loss point for frequency in AC mode not consistent in parallel systems
49 High loss point for voltage in AC mode not consistent in parallel systems
50 Low loss point for voltage in AC mode not consistent in parallel systems
51 Warning for locking in bypass mode after 3 consecutive overloads within 30 min
52 Warning for three-phase AC input current unbalance
53 Warning for a three-phase input current unbalance detected in battery mode
54 Warning for Inverter inter-current unbalance
55 Programmable outlets cut off pre-alarm
56 Warning for Battery replace
57 Abnormal warning on input phase angle
58 Warning!! Cover of maintain switch is open
62 EEPROM operation error


Daniele Pezzini <hyouko@gmail.com>

•Arnaud Quette <arnaud.quette@gmail.com>

•John Stamp <kinsayder@hotmail.com>

•Peter Selinger <selinger@users.sourceforge.net>

•Arjen de Korte <adkorte-guest@alioth.debian.org>

•Alexander Gordeev <lasaine@lvk.cs.msu.su>

•Edgar Fuß <ef@math.uni-bonn.de>

blazer_ser(8), blazer_usb(8), nutupsdrv(8), ups.conf(5), upsc(8), upscmd(8), upsdrvctl(8), upsmon(8), upsrw(8)

•The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

•The NUT HCL: http://www.networkupstools.org/stable-hcl.html
01/25/2023 Network UPS Tools 2.8.0